6907996 mRB6-16-3N-B-03-A-PV-FL

General specifications
Product name
Eaton Systeem 55 LV systems Final Distribution Boards
Part no.
mRB6-16-3N-B-03-A-PV-FL
EAN
9010653026273
Product Length/Depth
60 millimetre
Product height
80 millimetre
Product width
70 millimetre
Product weight
0.5333 kilogram
Compliances
RoHS conform
Product Tradename
Systeem 55
Product Type
LV systems
Product Sub Type
Final Distribution Boards
Countries
Netherlands
Product Specification Details
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Built-in depth
60 mm
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Current limiting class
3
Degree of protection
IP20
Disconnection characteristic
Other
Fault current rating
0.3 A
Features
Concurrently switching N-neutral
Frequency rating
50 Hz
Leakage current type
A
Nominal current
16 A
Number of poles
Three-pole + N
Number of poles (protected)
3
Number of poles (total)
4
Operating ambient temperature - max
40 °C
Operating ambient temperature - min
-25 °C
Overvoltage category
III
Pollution degree
2
Power loss
0 W
Rated current
16 A
Rated fault current (mA) - max
300 mA
Rated impulse withstand voltage (Uimp)
4 kV
Rated insulation voltage (Ui)
440 V
Rated operational voltage (Ue) - max
400 V
Rated short-circuit breaking capacity (EN 61009)
6 kA
Rated short-circuit breaking capacity (EN 61009-1)
6 kA
Rated short-circuit breaking capacity (IEC 60947-2)
0 kA
Rated switching capacity (IEC/EN 60947-2)
6 kA
Release characteristic
B
Surge current capacity
0.25 kA
Tripping characteristic
B
Voltage type
AC
Width in number of modular spacings
4

Technical data ETIM 8.0

Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination (ecl@ss10.0.1-27-14-22-07 [AFZ810015])
Number of poles (total)
4
Number of protected poles
3
Rated voltage
400 V
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.3 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity according to EN 61009
6 kA
Rated short-circuit breaking capacity according to IEC 60947-2
0 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Disconnection characteristic
Other
Surge current capacity
0.25 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
B
Concurrently switching neutral conductor
Yes
With interlocking device
No
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
-25 - 40 °C
Width in number of modular spacings
4
Built-in depth
60 mm
Flush-mounted installation
No
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
1 - 25 mm²
Connectable conductor cross section multi-wired
1 - 25 mm²