Catalog navigation
All catalogs
Geometric Search
CAD model selection
Add for comparison
Selectable products: 1
Company
ABB Low Voltage & Systems
Description
CM-PVx - Three Phase Monitors
Bill of material
ABB - 1SVR730794R2300 + CM-PVS.81S Three-phase monitoring relay 2c/o, 0,0,1-30s, L1-L2-L3=3x200-400VAC
Product ID
1SVR730794R2300
Extended Product Type
CM-PVS.81S
Invoice Description
CM-PVS.81S Three-phase monitoring relay 2c/o, 0,0,1-30s, L1-L2-L3=3x200-400VAC
Description
Three-phase monitoring relay
Long Description
The CM-PVS.81S relay is from the CM three-phase monitors range. This relay operates with a rated control supply voltage / three-phase measuring voltage of 200-400 V AC and has a 2 c/o output with contacts rated at 250 V / 4 A. The CM-PVS.81S monitors the phase parameters over/undervoltage and phase failure. The corresponding threshold values are adjustable. Phase sequence monitoring as well as an ON or OFF tripping delay are selectable. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
International product number
4016779876483
Product number of the Manufacturer
1SVR730794R2300
Type of electric connection
Screw connection
With detachable clamps
false
Rated control supply voltage Us at AC 50HZ
200 - 400 V
Rated control supply voltage Us at AC 60HZ
200 - 400 V
Rated control supply voltage Us at DC
- - - V
Voltage type for actuating
AC
Phase sequence monitoring
true
Phase failure detection
true
Function under voltage detection
true
Function over voltage detection
true
Phase imbalance monitoring
false
Voltage measuring range
200 - 400 V
Min. adjustable delay-on energization time
0.2 s
Max. permitted delay-on energization time
0.2 s
Min. adjustable off-delay time
0.1 s
Max. permitted off-delay time
30 s
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0
Number of contacts as change-over contact
2
Width
22.5 mm
Height
85.6 mm
Depth
103.7 mm
Customs tariff number
85364900
Deeplink product page
Link to product detail page
Type
CM-PVS.81S
Procurement
Last updateJul 25, 2025, 10:00 AM
Part number1SVR730794R2300
All information without guarantee
Last update: Jul 25, 2025, 10:00 AM
Preview - Generation
Preview
3D
2D

Classifications
ETIM 10.0
Phase monitoring relay:
Width: 22.5 mm
Height: 85.6 mm
Depth: 103.7 mm
Voltage measuring range: 200 - 400 V
With detachable clamps: false
Phase sequence monitoring: true
Phase failure detection: true
Function under voltage detection: true
Function overvoltage detection: true
Phase imbalance monitoring: false
Type of electric connection: Screw connection
Max. permitted delay-on energization time: 0.2 s
Min. adjustable delay-on energization time: 0.2 s
Max. permitted off-delay time: 30 s
Min. adjustable off-delay time: 0.1 s
Number of contacts as normally closed contact: 0
Number of contacts as normally open contact: 0
Number of contacts as change-over contact: 2
CNS
Object Properties:
Order Number: 1SVR730794R2300
Description long: The CM-PVS.81S relay is from the CM three-phase monitors range. This relay operates with a rated control supply voltage / three-phase measuring voltage of 200-400 V AC and has a 2 c/o output with contacts rated at 250 V / 4 A. The CM-PVS.81S monitors the phase parameters over/undervoltage and phase failure. The corresponding threshold values are adjustable. Phase sequence monitoring as well as an ON or OFF tripping delay are selectable. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
Description short: CM-PVS.81S Three-phase monitoring relay
Manufacturer / brand name: ABB
Product website: https://new.abb.com/products/ABB1SVR730794R2300
Customs Tariff Number: 85364900
GTIN-Code: 4016779876483
ETIM 8.0
Phase monitoring relay:
Width: 22.5 mm
Height: 85.6 mm
Depth: 103.7 mm
Voltage measuring range: 200 - 400 V
With detachable clamps: false
Phase sequence monitoring: true
Phase failure detection: true
Function under voltage detection: true
Function over voltage detection: true
Phase imbalance monitoring: false
Type of electric connection: Screw connection
Rated control supply voltage Us at AC 50HZ: 200 - 400 V
Rated control supply voltage Us at AC 60HZ: 200 - 400 V
Rated control supply voltage Us at DC: - - - V
Max. permitted delay-on energization time: 0.2 s
Min. adjustable delay-on energization time: 0.2 s
Max. permitted off-delay time: 30 s
Min. adjustable off-delay time: 0.1 s
Voltage type for actuating: AC
Number of contacts as normally closed contact: 0
Number of contacts as normally open contact: 0
Number of contacts as change-over contact: 2
ETIM 9.0
Phase monitoring relay:
Width: 22.5 mm
Height: 85.6 mm
Depth: 103.7 mm
Voltage measuring range: 200 - 400 V
With detachable clamps: false
Phase sequence monitoring: true
Phase failure detection: true
Function under voltage detection: true
Function over voltage detection: true
Phase imbalance monitoring: false
Type of electric connection: Screw connection
Rated control supply voltage AC 50 Hz: 200 - 400 V
Rated control supply voltage AC 60 Hz: 200 - 400 V
Rated control supply voltage DC: - - - V
Max. permitted delay-on energization time: 0.2 s
Min. adjustable delay-on energization time: 0.2 s
Max. permitted off-delay time: 30 s
Min. adjustable off-delay time: 0.1 s
Voltage type for actuating: AC
Number of contacts as normally closed contact: 0
Number of contacts as normally open contact: 0
Number of contacts as change-over contact: 2
eclass
27-37-18-03 - Asymmetry monitoring equipment:
function over-voltage detection present: true
max. rated control supply voltage Us: 200 - 400 V
max. voltage measuring range: 200 - 400 V
min. rated control voltage Us with AC 50 Hz: 200 - 400 V
min. rated control voltage Us with AC 60 Hz: 200 - 400 V
min. rated control voltage Us with DC: - - - V
min. voltage measuring range: 200 - 400 V
Number of breaking contacts: 0
Number of changers: 2
Number of making contacts: 0
height: 85.6 mm
depth: 103.7 mm
Type of actuation: AC
Max. response delay: 0.2 s
Max. delay time: 30 s
Min. response delay: 0.2 s
Min. delay time: 0.1 s
detachable terminals present: false
Design of electrical connection: Screw connection
width: 22.5 mm
Phase sequence monitoring: true
Phase failure recognition possible: true
function undervoltage recognition present: true
Asymmetry recognition present: false