Catalog navigation
All catalogs
Geometric Search
CAD model selection
Add for comparison
Selectable products: 1
Company
ABB Low Voltage & Systems
Description
AS09 - 3-pole Contactors - AC Operated
Bill of material
ABB - 1SBL101001R2001 + AS09-30-01-20 24V50/60HZ Contactor
Product ID
1SBL101001R2001
Extended Product Type
AS09-30-01-20
Invoice Description
AS09-30-01-20 24V50/60HZ Contactor
Description
Screw terminals
Long Description
AS09 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. The AS... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
International product number
3471523033207
Product number of the Manufacturer
1SBL101001R2001
Rated control supply voltage Us at AC 50HZ
24 - 24 V
Rated control supply voltage Us at AC 60HZ
24 - 24 V
Rated control supply voltage Us at DC
- - - V
Voltage type for actuating
AC
Rated operation current Ie at AC-1, 400 V
22 A
Rated operation current Ie at AC-3, 400 V
9 A
Rated operation power at AC-3, 400 V
4 kW
Modular version
false
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
1
Type of electrical connection of main circuit
Screw connection
Number of normally closed contacts as main contact
0
Number of normally open contacts as main contact
3
Customs tariff number
85364900
Deeplink product page
Link to product detail page
Type
AS 09-30-01
Procurement
Last updateJul 25, 2025, 9:55 AM
Part number1SBL101001R2001
All information without guarantee
Last update: Jul 25, 2025, 9:55 AM
Preview - Generation
Preview
3D
2D
The preview does not represent the part configuration anymore.You have to generate a new preview.

Classifications
ETIM 10.0
Power contactor, AC switching:
Suitable for distribution board: false
Rated operation power at AC-3, 400 V: 4 kW
Number of normally open contacts as main contact: 3
Number of normally closed contacts as main contact: 0
Number of auxiliary contacts as normally open contact: 0
Number of auxiliary contacts as normally closed contact: 1
Rated operation current Ie at AC-3, 400 V: 9 A
Rated operation current Ie at AC-1, 400 V: 22 A
Rated control supply voltage AC 50 Hz: 24 - 24 V
Rated control supply voltage AC 60 Hz: 24 - 24 V
Rated control supply voltage DC: - - - V
Type of electrical connection of main circuit: Screw connection
Voltage type for actuating: AC
CNS
Object Properties:
Order Number: 1SBL101001R2001
Description long: AS09 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. The AS... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
Description short: AS09-30-01-20 24V50/60HZ Contactor
Manufacturer / brand name: ABB
Product website: https://new.abb.com/products/ABB1SBL101001R2001
Customs Tariff Number: 85364900
GTIN-Code: 3471523033207
ETIM 8.0
Power contactor, AC switching:
Modular version: false
Rated operation power at AC-3, 400 V: 4 kW
Number of normally open contacts as main contact: 3
Number of normally closed contacts as main contact: 0
Number of auxiliary contacts as normally open contact: 0
Number of auxiliary contacts as normally closed contact: 1
Rated operation current Ie at AC-3, 400 V: 9 A
Rated operation current Ie at AC-1, 400 V: 22 A
Rated control supply voltage Us at AC 50HZ: 24 - 24 V
Rated control supply voltage Us at AC 60HZ: 24 - 24 V
Rated control supply voltage Us at DC: - - - V
Type of electrical connection of main circuit: Screw connection
Voltage type for actuating: AC
ETIM 9.0
Power contactor, AC switching:
Modular version: false
Rated operation power at AC-3, 400 V: 4 kW
Number of normally open contacts as main contact: 3
Number of normally closed contacts as main contact: 0
Number of auxiliary contacts as normally open contact: 0
Number of auxiliary contacts as normally closed contact: 1
Rated operation current Ie at AC-3, 400 V: 9 A
Rated operation current Ie at AC-1, 400 V: 22 A
Rated control supply voltage AC 50 Hz: 24 - 24 V
Rated control supply voltage AC 60 Hz: 24 - 24 V
Rated control supply voltage DC: - - - V
Type of electrical connection of main circuit: Screw connection
Voltage type for actuating: AC
cadenas_class
:
eclass
27-37-10-03 - Power contactor, AC switching:
Rated operating power with AC-3, 400 V: 4 kW
Rated operating current Ie with AC-1, 400 V: 22 A
Rated operating current Ie with AC-3, 400 V: 9 A
max. rated control supply voltage Us: 24 - 24 V
min. rated control voltage Us with AC 50 Hz: 24 - 24 V
min. rated control voltage Us with AC 60 Hz: 24 - 24 V
min. rated control voltage Us with DC: - - - V
Number of auxiliary contacts as opener: 1
Number of auxiliary contacts as shutter: 0
Number of main contacts as opener: 0
Number of making contacts and main contacts: 3
Type of actuation: AC
Connection type: Screw connection
suitable for series installation: false