177860 FRBM6-D16/1N/003-G/A
RCD/MCB combination, 16 A, 30 mA, MCB trip characteristic: D, 1p+N, RCD trip characteristic: G/A
High-quality residual current device/miniature circuit breaker combination, line voltage-independent, contact position indicator red - green, terminal rear plug protection, tri-stable slide catch - enables removal from existing busbar system, comprehensive range of accessories suitable for subsequent installation, wide range of rated fault currents, rated operational currents up to 40 A, tripping characteristics B, C, D, rated breaking capacity 6 kA, suitable for outdoor use (on-site power and outdoor distribution board) up to -25 °C
General specifications
Product name
Eaton Moeller series xEffect - FRBm6/M RCBO - residual-current circuit breaker with overcurrent protection
Part no.
FRBM6-D16/1N/003-G/A
EAN
4015081724338
Product Length/Depth
80 millimetre
Product height
75 millimetre
Product width
35 millimetre
Product weight
0.216 kilogram
Compliances
RoHS conform
Certifications
CE
Product Tradename
xEffect - FRBm6/M
Product Type
RCBO - Residual-current circuit breaker with overcurrent protection
Product Sub Type
None
Delivery program
Application
Switchgear for industrial and advanced commercial applications
Basic function
Combined RCD/MCB devices
Number of poles
Single-pole + N
Number of poles (protected)
1
Number of poles (total)
2
Release characteristic
D
Amperage Rating
16 A
Rated current
16 A
Fault current rating
0.03 A
Type
RCBO
Technical Data - Electrical
Voltage type
AC
Voltage rating
240 V - 240 V
Rated operational voltage (Ue) - max
240 V
Rated insulation voltage (Ui)
500 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating
50 Hz
Leakage current type
A
Rated short-circuit breaking capacity (EN 60947-2)
0 kA
Rated short-circuit breaking capacity (EN 61009)
6 kA
Rated short-circuit breaking capacity (EN 61009-1)
6 kA
Rated short-circuit breaking capacity (IEC 60947-2)
0 kA
Surge current capacity
3 kA
Disconnection characteristic
Short-time delayed
Pollution degree
2
Technical Data - Mechanical
Width in number of modular spacings
2
Built-in depth
75.5 mm
Degree of protection
IP20
Connectable conductor cross section (solid-core) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (multi-wired) - max
25 mm²
Design verification as per IEC/EN 61439 - technical data
Rated operational current for specified heat dissipation (In)
16 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
3.6 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Additional information
Current limiting class
3
Features
Anti-nuisance tripping version
Concurrently switching N-neutral
Concurrently switching N-neutral
Technical data ETIM 9.0
Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination (ecl@ss13-27-14-22-07 [AFZ810020])
Number of poles (total)
2
Number of protected poles
1
Rated voltage
240 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Power loss
W
Rated short-circuit breaking capacity according to EN 61009
6 kA
Rated short-circuit breaking capacity according to IEC 60947-2
0 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Disconnection characteristic
Short-time delayed
Surge current capacity
3 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
D
Concurrently switching neutral conductor
Yes
With interlocking device
No
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
-25 - 40 °C
Width in number of modular spacings
2
Built-in depth
75.5 mm
Flush-mounted installation
No
Anti-nuisance tripping version
Yes
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
1 - 25 mm²
Connectable conductor cross section multi-wired
1 - 25 mm²
-
Eaton EMEA Download-Center - download data for this item
-