1742432 mRB6-16-3N-C-003-A-FL

General specifications
Product name
Eaton Systeem 55 FLEX residual current circuit-breaker
Part no.
mRB6-16-3N-C-003-A-FL
EAN
8711426741553
Product Length/Depth
146 millimetre
Product height
74 millimetre
Product width
84 millimetre
Product weight
0.22 kilogram
Compliances
RoHS conform
Product Tradename
Systeem 55
Product Type
FLEX
Product Sub Type
Residual current circuit-breaker
Product Specification Details
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Amperage Rating
16 A
Built-in depth
70 mm
Class
A
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Current limiting class
3
Degree of protection
IP20
Disconnection characteristic
Other
Fault current rating
30 mA
Features
Concurrently switching N-neutral
Residual current circuit breaker
Frequency rating
50 Hz
Leakage current type
A
Nominal current
16 A
Number of poles
Three-pole + N
Number of poles (protected)
1
Number of poles (total)
4
Operating ambient temperature - max
40 °C
Operating ambient temperature - min
-25 °C
Overvoltage category
II
Pollution degree
3
Power loss
0 W
Rated current
16 A
Rated fault current (mA) - max
30 mA
Rated impulse withstand voltage (Uimp)
4 kV
Rated insulation voltage (Ui)
500 V
Rated operational voltage (Ue) - max
400 V
Rated short-circuit breaking capacity (EN 61009)
6 kA
Rated short-circuit breaking capacity (EN 61009-1)
6 kA
Rated short-circuit breaking capacity (IEC 60947-2)
0 kA
Rated switching capacity (IEC/EN 60947-2)
6 kA
Release characteristic
C
Special features
Residual current circuit breaker FLEX
Surge current capacity
6 kA
Tripping characteristic
C
Type
Flex components DIN-modular Combined RCD/MCB circuit breaker
Used with
DIN-modular
Flex components
Voltage type
AC
Width in number of modular spacings
4

Technical data ETIM 8.0

Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination (ecl@ss10.0.1-27-14-22-07 [AFZ810015])
Number of poles (total)
4
Number of protected poles
1
Rated voltage
400 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity according to EN 61009
6 kA
Rated short-circuit breaking capacity according to IEC 60947-2
0 kA
Rated short-circuit breaking capacity Icn according to EN 61009-1
6 kA
Disconnection characteristic
Other
Surge current capacity
6 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
C
Concurrently switching neutral conductor
Yes
With interlocking device
No
Over voltage category
2
Pollution degree
3
Ambient temperature during operating
-25 - 40 °C
Width in number of modular spacings
4
Built-in depth
70 mm
Flush-mounted installation
No
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
1 - 25 mm²
Connectable conductor cross section multi-wired
1 - 25 mm²